  • Home
  • Introduction
    • Safety
      • General safety references
        • Also observe the following technical documents
      • Required tools and kit content
        • Switch off compressor, depressurize, extract refrigerant
          • Remove existing compressor protection device (SE-E*)
            • Installing SE-i1 with full sensor kit
              • Inside the terminal box of compressor
                • Outside the terminal box for A3 regrigerants
                • BEST SOFTWARE settings
                  • Compressor data on name plate
                  • Check compressor for tightness, evacuate and charge refrigerant
                    • Schematic wiring diagrams
                      • CS.65 .. 95 with SE-i1, PW start, stepless capacity control, full sensor kit
                        • CS.65 .. 95 with SE-i1, Y/Δ start, stepped capacity control, full sensor kit
                        • Dimensional drawing SE-i1
                          • Connection positions of the high and low pressure transmitter for CS. compressors