Remove the old oil filter

Authorized staff

All work done on the products and the systems in which they are or will be installed may only be performed by qualified and authorised staff who have been trained and instructed in all work. The qualification and competence of the qualified staff must correspond to the local regulations and guidelines.

The oil filter chamber and the compressor are pressure chambers independent of each other!
warning

The oil filter chamber and the compressor are pressure chambers independent of each other!

Serious injuries are possible.

For maintenance work, relieve separately the compressor and the oil filter chamber of pressure!

Wear safety goggles!

Loosen screws at the flange

Pull out flange upwards

Pull out oil filter and drain

Replace the oil filter

Remove old gasket

Carfully remove old gasket!
Do not damage/scratch sealing surface!

Carfully remove old gasket!
Do not damage/scratch sealing surface!

Clean sealing surface