Recommended start and stop sequences

Life-threatening voltages inside the frequency inverter housing!
danger

Life-threatening voltages inside the frequency inverter housing!

Contact can lead to serious injuries or death.

Never open the FI housing in operation! Switch off the main switch and secure it against being switched on again.

Wait for at least 10 minutes until all capacitors have been discharged!

Before switching on again, close the FI housing.

In operation, the heat sink of the frequency inverter will get hot.
caution

In operation, the heat sink of the frequency inverter will get hot.

Risk of burns upon contact!

Prior to performing work on the frequency inverter, disconnect the power supply and wait for at least 15 minutes until the heat sink has cooled down.

Risk of compressor failure!

Risk of compressor failure!

Operate the compressor only in the intended rotation direction!

The following diagrams show some examples for start and stop sequences. They enable a soft start, but also a sufficient oil supply for the compressor.

During operation, frequency changes should be much slower than during start and stop (Configuration of the frequency inverter).

Apart from the exceptions explained below:

Compressor and motor damage!

Compressor and motor damage!

Do not combine a frequency inverter with mechanical capacity control of the compressor! Especially at low speed, adequate motor cooling is not guaranteed because refrigerant mass flow is heavily reduced. Certain exceptions for screw compressors are possible in consultation with Bitzer.

If the compressor is operated with the CM-SW-01 module and frequency inverter mode, the module controls the mechanical capacity sliders and the oil solenoid valve.

Compressors CS.65 .. 95

Start sequence:

Recommended start sequence for compressors CS.65 .. 95 with frequency inverter (FI). Start the CR slider unloaded, turn FI to minimum speed of 25 Hz in max. 2 sec, then switch on the CR solenoid valves up to 100% (see Operating Instructions SB-170, for start/stop only valve CR3 is energised, CR4 may be energised continuously instead of intermittently with FI operation). The compressor should then reach the application limits within max. 2 min.

For special operating conditions at high evaporation and condensing temperatures the frequency inverter may be combined with CR 75%. In the following diagram showing application limits, this is the white area at the bottom right (for application limits, see also above):

Stop sequence:

Recommended stop sequence for compressors CS.65 .. 95 with frequency inverter (FI). After the FI is switched off, the CR slider moves back passively to 25% within approx. 5 min, valve CR3 remains energised (see Operating Instructions SB-170).

Compressors CS.105 and HS.95 with CM-SW-01 module

Recommended start and stop sequence for compressors CS.105 and HS.95 with frequency inverter (FI) and compressor module CM-SW-01 in "Frequency inverter" mode. The module controls the oil management as well as the CR solenoid valves for capacity control (see Operating Instructions SB-170 for CS.105 and SB-110 for HS.95).

The combination of frequency inverter and slider capacity regulation is not authorised for CS. and HS. compressors with CM-SW-01. After compressor start, the sliders automatically move to full load position, after compressor stop they are not actively unloaded. This enables a faster new start because the capacity control by frequency inverter can start directly – without increased risk of the compressor not reaching its operating limits in time.

Compressors HS.53 .. 74 and OS.53 .. 74

Start sequence:

Recommended start sequence for compressors OS.53 .. 74, HS.53 .. 74 with frequency inverter (FI). Start the control pistons unloaded, open the oil solenoid valve as soon as the FI reaches 15 Hz. At minimum speed (20 Hz for HS., 25 Hz for OS.) switch on the control pistons up to 100% (see Operating Instructions SB-100 for HS. and SB-500 for OS.).

Stop sequence:

Recommended stop sequence for compressors OS.53 .. 74, HS.53 .. 74 with frequency inverter (FI). After the FI is switched off, the control pistons move back passively to 50%.

Compressors HS.85 and OS.85 (without CM-SW-01 module)

Start sequence:

Recommended start sequence for compressors HS.85 and OS.85 with frequency inverter (FI). Start the CR slider unloaded. As soon as the FI reaches its minimum speed (20 Hz for HS., 25 Hz for OS.), switch on the solenoid valves to 100% as explained in Operating Instructions SB-110 resp. SB-520 (CR4 resp. Y4 intermittent). Since the compressors are equipped with an integrated oil management system, there is no need to consider a regulation of the oil solenoid valve.

Stop sequence:

Recommended stop sequence for compressors HS.85 and OS.85 with frequency inverter (FI). After the FI is switched off, the CR slider moves back passively to 25%.

Compressors OS.A85 .. 105 with CM-SW-01 module

While the integrated motor of the semi-hermetic CS. and HS. compressors provide enough reserve for pull down conditions, this isn't necessarily the case for the OS. compressors: Here, the motor can be selected for the specific application, e.g. a relatively small one might be used for low temperature applications. As a result, it may be necessary to reduce the load by slider control until nominal operating conditions are reached, in order to not overload the motor. Since the motor cooling with very low refrigerant mass flow is not such an important issue for open drive compressors as it is for CS. and HS. compressors, slider capacity control can be combined with frequency inverter control for pull down conditions. In this case, the minimum slider capacity position is limited to 50%.

Start sequence:

Recommended start sequence for compressors OS.A85 .. 105 with frequency inverter (FI) and compressor module CM-SW-01. The module controls the oil management as well as the CR solenoid valves for capacity control (see Operating Instructions SB-520). In "Frequency inverter" mode the module is preset so that it puts the CR slider for start unloading to min. 50% instead of 25% (50 .. 100% may be chosen).

Stop sequence:

Recommended stop sequence for compressors OS.A85 .. 105 with frequency inverter (FI) and compressor module CM-SW-01. The module controls the oil management as well as the CR solenoid valves (see Operating Instructions SB-520). In "Frequency inverter" mode the module is preset so that it puts the CR slider for start unloading to min. 50% instead of 25% (50 .. 100% may be chosen).

Start / Stop sequences with economiser operation

In principle, the above sequences apply also to economiser operation, but observe the altered application limits (see Bitzer Software)! The economiser may be started as soon as operating conditions are stable, and is shut off together with the frequency inverter.

OS.A95 and OS.A105: Pulsation muffler during economiser operation

For OS.A95 and OS.A105 compressors in ECO operation, a pulsation muffler in the economiser line is recommended resp. necessary. Two options are available:

Muffler system, consisting of muffler, check valve, control valve
Basic pulsation muffler SD42 in the ECO connection, part no. 354 004 05

For operation at condensing temperatures > 40°C and/or evaporation temperatures > 10°C, the muffler system is mandatory. In the remaining range, BITZER recommends the pulsation muffler SD42. For details see the following figure and table.

Application limit of OS.A95 and OS.A105 screw compressors during ECO operation, In the shaded area. the ECO muffler system is mandatory.
OS.A95 and OS.A105 compressors during ECO operation: recommended pulsation mufflers and combination with capacity regulation

Planned operating range

Pulsation muffler

Possible scope of capacity regulation

Operation in the shaded area of the application limit (tc > 40°C and/or to > 10°C)

Economiser muffler system is mandatory

  • Slider 80% .. 100% and fixed frequency 50/60 Hz
  • or slider 100% and variable frequency 25 .. 67 Hz

Operation outside the shaded area of the application limit (tc < 40°C and to < 10°C)

Optional: economiser muffler system

  • Slider 80% .. 100% and fixed frequency 50/60 Hz
  • or slider 100% and variable frequency 25 .. 67 Hz

Optional: basic pulsation muffler SD42 in ECO connection

  • Slider 80% .. 100% and fixed frequency 50/60 Hz

See also:

Start and stop in compound systems