Oils for refrigerant R744 (CO2)
Characterising the oils
Oil | Oil type | Applications | Designation on compressor |
---|---|---|---|
BSE60K | polyolester oil (POE) | standard oil charge for subcritical (e.g. cascade) applications | "K" (e.g. 4DSL‑10K) |
BSE85K | polyolester oil (POE) | standard oil charge for transcritical applications, | "K" (e.g. 4FTE‑30K) |
BSG68K | polyalkylene glycol oil (PAG) | standard oil charge and precondition fo applications with low pressure > 40 bar / high pressure > 120 bar, | "Z" (e.g. 4MTEU‑10LZ) |
Material safety data sheets
Apart from this document, please observe the material safety data sheet (MSDS) for the respective oil. It contains information on toxicity, handling, personal protective equipment and disposal of the oil. Material safety data sheets for all Bitzer oils are available on request.
Application range
Oil | Air conditioning | Medium temperature application | Low temperature application |
---|---|---|---|
BSE60K | – – | – – | ✔ |
BSE85K | (✔) | ✔ | ✔ |
BSG68K | ✔* | ✔ | ✔ |
Technical data
BSE60K | BSE85K | BSG68K | Unit | |
---|---|---|---|---|
Density at 15°C | 1.009 | 0.993 | 1.003 | g/ml |
Flashpoint | 286 | 246 | > 200 | °C |
Pour point | -48 | -42 | -46 | °C |
Kinematic viscosity | ||||
at 40°C | 55 | 80 | 68 | cSt |
at 100°C | 9 | 11 | 16 | cSt |
Miscibility gaps
Refrigerant solubility in oil
The following diagrams can be used to read off the refrigerant content in the lubricant depending on refrigerant pressure and oil temperature.
Warning values for used oils
The listed polyolester oils and the polyalkylene glycol oil are categorized as group KB according to DIN51503, Part 1. To determine the used condition of the oil, e.g. with respect to water content or total acid number (TAN), the reference values of DIN 51503, Part 2, apply.
Oil | Kinematic viscosity at 40°C (DIN EN ISO3104) | Max. water content | Total acid number |
---|---|---|---|
BSE60K | outside of 47 .. 63 cSt (*) | 150 mg H2O/kg oil | 0.2 mg KOH/g |
BSE85K | outside of 68 .. 92 cSt (*) | 150 mg H2O/kg oil | 0.2 mg KOH/g |
BSG68K | outside of 58 .. 78 cSt (*) | 800 mg H2O/kg oil | 0.2 mg KOH/g |
Elastomer compatibility
Relevant literature recommends the following seaI materials for polyolester oils (POE) and polyalkylene glycol oils (PAG) with R744:
- hydrogenated acrylonitrile butadiene rubber, nitrile content >36%
- ethylene propylene diene rubber
- fluorinated rubber