R404A and alternative refrigerants
The following table shows all available data for R404A and alternative refrigerants.
ODP: ozone depletion potential
GWP: global warming potential according to EN 378:2017; AR4: Fourth Assessment Report of the IPCC, AR5: Fifth Assessment Report of the IPCC
pract. limit AEL: assigned exposure limit according to EN 378:2017
Temperature glide: Total glide from bubble to dew line, based on 1.013 bar. Real glide depends on operating conditions.
Relative refr. capacity and discharge temp. increase: Reference refrigerants are those listed under "Substitute for", performance data are average values based on calorimeter tests.
(H): high temperature application
(M): medium temperature application
(L): low temperature application
Data is based on publications of various refrigerant manufacturers and is subject to change.
R404A | R448A | R449A | R452A | R454A | R454C | R455A | R457A | R465A | R468A | R290 | R1270 | R717 | R723 | R744 | |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Refrigerant | R404A | R448A | R449A | R452A | R454A | R454C | R455A | R457A | R465A | R468A | R290 | R1270 | R717 | R723 | R744 |
Chemical | CH3CH2CH3 | CH2CHCH3 | NH3 | NH3/ R-E170 | CO2 | ||||||||||
Group | HFC | HFO/ HFC | HFO/ HFC | HFO/ HFC | HFO/ HFC | HFO/ HFC | HFO/ HFC | HFO/ HFC | HFO/ HFC | HFO/ HFC | HC | HC | NH3 | NH3/ R-E170 | CO2 |
Components | R143a/ 125/ 134a | R32/ 125/ 1234yf/ 1234ze(E)/ 134a | R32/ 125/ 1234yf/ 134a | R32/ 125/ 1234yf | R32/ 1234yf | R32/ 1234yf | R32/ 1234yf/ 744 | R32/ 1234yf/ 152a | R32/ 1234yf/ 290 | R32/ 1234yf/ 1132a | |||||
Name | N-40 | XP40, 449A | XP44 | XL40, ARM-20b | XL20 | L-40X | ARM-20a | ARM-25 | propane | propylene / propene | ammonia | ammonia/ DME | carbon dioxide | ||
Manufacturer | Honeywell | Chemours, Arkema | Chemours | Chemours, Arkema | Chemours | Honeywell | Arkema | Arkema | Daikin Chemical | ||||||
Substitute for | R502, R22 | R404A, R507A | R404A, R507A | R404A, R507A | R404A, R507A | R404A, R507A | R404A, R507A | R404A, R507A | R404A, R507A | R404A, R507A, R22 | R404A, R507A, R22 | R404A, R507A, R22 | R404A, R507A, R22 | R404A, R507A, R22 | R23, R134a, R404A, R507A |
Application max (°C) | 0 | 12 | 12 | 12 | 12 | 12 | 12 | 12 | 7 | 0 | 12 | 12 | 12 | 12 | 20 |
Application min (°C) | -45 | -40 | -40 | -40 | -40 | -40 | -40 | -40 | -40 | -40 | -40 | -40 | -20 | -20 | -20 |
Appl. limitations max (°C) | 7 | ||||||||||||||
Appl. limitations min (°C) | -45 | -45 | |||||||||||||
Appl. 2-stage max (°C) | -30 | -25 | -25 | -25 | -25 | -25 | -25 | -25 | -20 | -20 | -15 | -15 | -10 | ||
Appl. 2-stage min (°C) | -70 | -65 | -65 | -65 | -65 | -65 | -65 | -65 | -55 | -55 | -50 | -50 | -50 | ||
Oil 1 | POE | POE | POE | POE | POE | POE | POE | POE | POE | POE | PAO | PAO | MO | MO | POE |
Oil 2 | PVE | PVE | PVE | PVE | PVE | PVE | PVE | PVE | PVE | PAG | PAG | PAO | PAO | PAG | |
Oil 3 | POE | POE | MO/HC | MO/HC | |||||||||||
Oil with limitations 1 | AB | AB | AB | AB | AB | ||||||||||
Oil with limitations 2 | MO | MO | |||||||||||||
Molar mass | 97,6 | 86,28 | 87,21 | 103,51 | 79,79 | 90,78 | 87,45 | 87,61 | 82,9 | 88,8 | 44,1 | 42,08 | 17,03 | 22,77 | 44,01 |
Normal boiling point (°C) | -46,2 | -46,1 | -45,7 | -46,9 | -47,9 | -45,6 | -52 | -42,6 | -51,7 | -51,2 | -42,1 | -47,6 | -33,4 | -36,5 | -78,3 |
Normal dew point (°C) | -45,5 | -39,9 | -40 | -43,1 | -42,2 | -37,8 | -39,2 | -35,5 | -40 | -39 | -42,1 | -47,6 | -33,4 | -36,5 | -78,3 |
Temperature glide (K) | 0,7 | 6,2 | 5,7 | 3,8 | 5,7 | 7,8 | 12,8 | 7,1 | 11,7 | 12,2 | 0 | 0 | 0 | 0 | 0 |
Crit. temp. (°C) | 72 | 83 | 82 | 75 | 82 | 86 | 86 | 90 | 82 | 84 | 97 | 91 | 132 | 131 | 31 |
Crit. pressure (bar) | 37,35 | 45,95 | 45 | 40,03 | 46,3 | 43,2 | 46,5 | 43,08 | 43,36 | 44,54 | 42,5 | 45,6 | 113 | 110 | 73,8 |
ODP | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
GWP AR4 | 3922 | 1387 | 1397 | 2140 | 239 | 148 | 148 | 139 | 145 | 148 | 3 | 2 | 0 | 1 | 1 |
GWP AR5 | 3940 | 1273 | 1282 | 1945 | 238 | 146 | 146 | 139 | 143 | 147 | 3 | 2 | 0 | 1 | 1 |
Cond. temp. at 26 bar abs (°C) | 56 | 58 | 58 | 56 | 57 | 64 | 61 | 68 | 60 | 62 | 70 | 61 | 60 | 58 | -11 |
Cond. temp. at 40 bar abs (°C) | 77 | 75 | 76 | 83 | 85 | ||||||||||
Relative refr. capacity (%) | 105 (M) | 96 (M) | 96 (M) | 93 (M) | 86 (M) | 104 (M) | 100 (M) | 105 (M) | |||||||
Discharge temp. increase (K) | -34 | 12 | 12 | 10 | 4 | 12 | 60 | 35 | |||||||
Safety group | A1 | A1 | A1 | A1 | A2L | A2L | A2L | A2L | A2 | A2L | A3 | A3 | B2L | B2 | A1 |
Pract. limit AEL (kg/m³) | 0,52 | 0,388 | 0,357 | 0,423 | 0,056 | 0,059 | 0,105 | 0,043 | 0,04 | N/A | 0,008 | 0,008 | 0,00035 | N/A | 0,07 |