R13, R23 and alternative refrigerants

The following table shows all available data for R13, R23 and alternative refrigerants.

ODP: ozone depletion potential
GWP: global warming potential according to EN 378:2017; AR4: Fourth Assessment Report of the IPCC, AR5: Fifth Assessment Report of the IPCC
pract. limit AEL: assigned exposure limit according to EN 378:2017
Temperature glide: Total glide from bubble to dew line, based on 1.013 bar. Real glide depends on operating conditions.
Relative refr. capacity and discharge temp. increase: Reference refrigerants are those listed under "Substitute for", performance data are average values based on calorimeter tests.
(H): high temperature application
(M): medium temperature application
(L): low temperature application
Data is based on publications of various refrigerant manufacturers and is subject to change.

R13, R23 and alternative refrigerants

R13

R23

R503

R508A

R508B

R744A

R170

Refrigerant

R13

R23

R503

R508A

R508B

R744A

R170

Chemical

CClF3

CHF3

N2O

CH3CH3

Group

CFC

HFC

CFC

HFC

HFC

N2O

HC

Components

R13/ 23

R23/ 116

R23/ 116

Name

chloro-trifluoro-methane

trifluoro-methane

nitrous oxide

ethane

Substitute for

R13, R503

R503

R503

R23, R508A, R508B

R23, R508A, R508B

Application max (°C)

-30

-50

-50

-50

-50

-40

-50

Application min (°C)

-80

-95

-90

-95

-95

-80

-95

Oil 1

MO

POE

AB

POE

POE

special

PAO

Oil 2

AB

PVE

MO

Oil 3

POE

Oil with limitations 1

AB

AB

Oil with limitations 2

Molar mass

104,46

70,01

87,24

100,1

95,39

44,01

30,07

Normal boiling point (°C)

-81,4

-82

-87,9

-87,6

-87,6

-88,5

-88,6

Normal dew point (°C)

-81,4

-82

-87,9

-87,6

-87,6

-88,5

-88,6

Temperature glide (K)

0

0

0

0

0

0

0

Crit. temp. (°C)

29

26

20

10

11

36

32

Crit. pressure (bar)

38,7

48,3

43,43

36,48

37,71

72,5

48,7

ODP

1

0

0,6

0

0

0,017

0

GWP AR4

14400

14800

14560

13210

13400

298

6

GWP AR5

13900

12400

13300

11600

11700

265

6

Cond. temp. at 26 bar abs (°C)

11

2

-2

-3

-3

-7

4

Safety group

A1

A1

A1

A1

A1

A1

A3

Pract. limit AEL (kg/m³)

0,5

0,68

0,35

0,23

0,25

N/A

0,0086