R12 and alternative refrigerants

The following table shows all available data for R12 and alternative refrigerants.

ODP: ozone depletion potential
GWP: global warming potential according to EN 378:2017; AR4: Fourth Assessment Report of the IPCC, AR5: Fifth Assessment Report of the IPCC
pract. limit AEL: assigned exposure limit according to EN 378:2017
Temperature glide: Total glide from bubble to dew line, based on 1.013 bar. Real glide depends on operating conditions.
Relative refr. capacity and discharge temp. increase: Reference refrigerants are those listed under "Substitute for", performance data are average values based on calorimeter tests.
(H): high temperature application
(M): medium temperature application
(L): low temperature application
Data is based on publications of various refrigerant manufacturers and is subject to change.

R12 and alternative refrigerants

R12

R134a

R22

R152a

R437A

R1234yf

Refrigerant

R12

R134a

R22

R152a

R437A

R1234yf

Chemical

CCl2F2

CF3CH2F

CHClF2

CHF2CH3

CF3FCH2

Group

CFC

HFC

HCFC

HFC

HFC

HFO

Components

R125/ 134a/ 600/ 601

Name

dichloro-difluoro-methane

1,1,1,2-tetrafluoro-ethane

chloro-difluoro-methane

1,1-difluoro-methane

2,3,3,3-tetrafluoro-1-propene

Manufacturer

Chemours, Honeywell

Substitute for

R12, R22

R502, R12

R12, R22

R12

R134a

Application max (°C)

20

25

12

25

12

25

Application min (°C)

-30

-20

-45

-20

-30

-25

Appl. limitations max (°C)

Appl. limitations min (°C)

-30

-30

Appl. 2-stage max (°C)

-20

Appl. 2-stage min (°C)

-50

Oil 1

MO

POE

MO

POE

POE

POE

Oil 2

AB

PVE

AB

PVE

PVE

PVE

Oil with limitations 1

AB

AB

AB

Oil with limitations 2

Molar mass

120,91

102,03

86,47

66,05

103,71

114,04

Normal boiling point (°C)

-29,8

-26,1

-40,7

-24

-32,4

-29,5

Normal dew point (°C)

-29,8

-26,1

-40,7

-24

-28,9

-29,5

Temperature glide (K)

0

0

0

0

3,5

0

Crit. temp. (°C)

112

101

96

113

95

95

Crit. pressure (bar)

41,2

40,7

49,9

45,2

40,03

33,8

ODP

1

0

0,055

0

0

0

GWP AR4

10900

1430

1810

124

1805

4

GWP AR5

10200

1300

1760

138

1640

1

Cond. temp. at 26 bar abs (°C)

86

79

63

85

75

82

Relative refr. capacity (%)

97 (M)

80 (L)

108 (M)

98 (M)

Discharge temp. increase (K)

-8

35

-7

-14

Safety group

A1

A1

A1

A2

A1

A2L

Pract. limit AEL (kg/m³)

0,5

0,25

0,3

0,027

0,081

0,058