Complete refrigerant data
The following table shows the complete data for all refrigerants considered, with a filter function and columns with comparative refrigerants as well as data ranges.
ODP: ozone depletion potential
GWP: global warming potential according to EN 378:2017; AR4: Fourth Assessment Report of the IPCC, AR5: Fifth Assessment Report of the IPCC
pract. limit AEL: assigned exposure limit according to EN 378:2017
Temperature glide: Total glide from bubble to dew line, based on 1.013 bar. Real glide depends on operating conditions.
Relative refr. capacity and discharge temp. increase: Reference refrigerants are those listed under "Substitute for", performance data are average values based on calorimeter tests.
(H): high temperature application
(M): medium temperature application
(L): low temperature application
Data is based on publications of various refrigerant manufacturers and is subject to change.
Refrigerant | similar to | similar to | similar to | similar to | GWP range | ODP | Temp. glide range (K) | Safety group | Chemical | Group | Components | Name | Manufacturer | Substitute for | Application max. (°C) | Application min. (°C) | Appl. limitation max. (°C) | Appl. limitation min. (°C) | Appl. 2-stage max. (°C) | Appl. 2-stage min. (°C) | GWP AR4 | GWP AR5 | Pract. limit AEL (kg/m3) | Molar mass | Normal boiling point (°C) | Normal dew point (°C) | Temp. glide (K) | Crit. temp. (°C) | Crit. pressure (bar) | Cond. temp. at 26 bar abs (°C) | Cond. temp. at 40 bar abs (°C) | Relative refr. capacity (%) | Discharge temp. increase(K) | Oil 1 | Oil 2 | Oil 3 | Oil with limitations 1 | Oil with limitations 2 |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
R11 | >2500 | 1 | 0 | A1 | CCl3F | CFC | trichloro-fluoro-methane | 30 | 0 | 4750 | 4660 | 0,3 | 137,37 | 23,8 | 23,8 | 0 | 198 | 44,1 | 163 | MO | AB | |||||||||||||||||
R12 | R134a | >2500 | 1 | 0 | A1 | CCl2F2 | CFC | dichloro-difluoro-methane | 20 | -30 | 10900 | 10200 | 0,5 | 120,91 | -29,8 | -29,8 | 0 | 112 | 41,2 | 86 | MO | AB | ||||||||||||||||
R13 | >2500 | 1 | 0 | A1 | CClF3 | CFC | chloro-trifluoro-methane | -30 | -80 | 14400 | 13900 | 0,5 | 104,46 | -81,4 | -81,4 | 0 | 29 | 38,7 | 11 | MO | AB | |||||||||||||||||
R13B1 | >2500 | 10 | 0 | A1 | CBrF3 | Halon | trifluoro-bromo-methane | -10 | -60 | 7140 | 6290 | 0,6 | 148,92 | -57,7 | -57,7 | 0 | 67 | 39,9 | 46 | MO | AB | |||||||||||||||||
R13I1 | ≤150 | 0,01 | 0 | A1 | CF3I | IFC | trifluoro-iodo-methane | 1 | 1 | N/A | 195,91 | -21,9 | -21,9 | 0 | 123 | 39,5 | 99 | POE | ||||||||||||||||||||
R14 | >2500 | 0 | 0 | A1 | CF4 | PFC | tetrafluoro-methane | -90 | -125 | 7390 | 6630 | 0,4 | 88,01 | -127,9 | -127,9 | 0 | -46 | 37,5 | -58 | POE | ||||||||||||||||||
R22 | R22 | >750..2500 | 0,055 | 0 | A1 | CHClF2 | HCFC | chloro-difluoro-methane | R502, R12 | 12 | -45 | -20 | -50 | 1810 | 1760 | 0,3 | 86,47 | -40,7 | -40,7 | 0 | 96 | 49,9 | 63 | 80 (L) | 35 | MO | AB | |||||||||||
R23 | >2500 | 0 | 0 | A1 | CHF3 | HFC | trifluoro-methane | R13, R503 | -50 | -95 | 14800 | 12400 | 0,68 | 70,01 | -82 | -82 | 0 | 26 | 48,3 | 2 | POE | PVE | AB | |||||||||||||||
R32 | R410A | >150..750 | 0 | 0 | A2L | CH2F2 | HFC | difluoro-methane | R410A | 15 | -15 | 675 | 677 | 0,061 | 52,02 | -51,7 | -51,7 | 0 | 78 | 57,8 | 42 | 61 | 108 (H) | 21 | POE | PVE | AB | |||||||||||
R123 | ≤150 | 0,02 | 0 | CClF2CClFH | HCFC | dichloro-trifluoro-ethane | R11 | 20 | 0 | 77 | 79 | 0,1 | 152,92 | 27,8 | 27,8 | 0 | 184 | 36,6 | 163 | MO | AB | |||||||||||||||||
R124 | >150..750 | 0,022 | 0 | A1 | CHClFCF3 | HCFC | chloro-tetrafluoro-ethane | R114, R12B1 | 40 | 5 | 609 | 527 | 0,11 | 136,47 | -12 | -12 | 0 | 122 | 36,2 | 105 | MO | AB | ||||||||||||||||
R125 | R404A | >2500 | 0 | 0 | A1 | CF3CHF2 | HFC | pentafluoro-ethane | 7 | -45 | 3500 | 3170 | 0,39 | 120,02 | -48,5 | -48,5 | 0 | 66 | 36,3 | 51 | POE | PVE | AB | |||||||||||||||
R134a | R134a | >750..2500 | 0 | 0 | A1 | CF3CH2F | HFC | 1,1,1,2-tetrafluoro-ethane | R12, R22 | 25 | -20 | -30 | 1430 | 1300 | 0,25 | 102,03 | -26,1 | -26,1 | 0 | 101 | 40,7 | 79 | 97 (M) | -8 | POE | PVE | AB | |||||||||||
R142b | >750..2500 | 0,065 | 0 | A2 | CClF2CH3 | HCFC | 1-chloro-1,1-difluoro-ethane | R114, R12B1 | 20 | -10 | 2310 | 1980 | 0,049 | 100,5 | -9,1 | -9,1 | 0 | 137 | 40,6 | 112 | MO | AB | ||||||||||||||||
R143a | >2500 | 0 | 0 | A2L | CF3CH3 | HFC | 1,1,1-trifluoro-ethane | 0 | -45 | 4470 | 4800 | 0,048 | 84,04 | -47,2 | -47,2 | 0 | 73 | 37,6 | 55 | POE | PVE | AB | ||||||||||||||||
R152a | R134a | ≤150 | 0 | 0 | A2 | CHF2CH3 | HFC | 1,1-difluoro-methane | R12, R22 | 25 | -20 | 124 | 138 | 0,027 | 66,05 | -24 | -24 | 0 | 113 | 45,2 | 85 | POE | PVE | AB | ||||||||||||||
R170 | ≤150 | 0 | 0 | A3 | CH3CH3 | HC | ethane | R23, R508A, R508B | -50 | -95 | 6 | 6 | 0,0086 | 30,07 | -88,6 | -88,6 | 0 | 32 | 48,7 | 4 | PAO | MO | POE | AB | ||||||||||||||
R227ea | >2500 | 0 | 0 | A1 | CF3CHFCF3 | HFC | 1,1,1,2,3,3,3-heptafluoro-propane | R12B1, R114 | 40 | -10 | 3220 | 3350 | 0,63 | 170,03 | -16,3 | -16,3 | 0 | 102 | 29,3 | 96 | POE | PVE | AB | |||||||||||||||
R236fa | >2500 | 0 | 0 | A1 | CF3CH2CF3 | HFC | 1,1,1,3,3,3-hexafluoro-propane | R114 | 40 | 0 | 9810 | 8060 | 0,59 | 152,04 | -1,5 | -1,5 | 0 | 125 | 32 | 115 | POE | PVE | AB | |||||||||||||||
R245fa | >750..2500 | 0 | 0 | B1 | CF3CH2CF2H | HFC | 1,1,1,3,3-pentafluoro-propane | R123 | 40 | 5 | 1030 | 856 | 0,19 | 134,05 | 15,1 | 15,1 | 0 | 154 | 36,5 | 136 | POE | |||||||||||||||||
R290 | R404A | R22 | ≤150 | 0 | 0 | A3 | CH3CH2CH3 | HC | propane | R404A, R507A, R22 | 12 | -40 | -20 | -55 | 3 | 3 | 0,008 | 44,1 | -42,1 | -42,1 | 0 | 97 | 42,5 | 70 | 86 (M) | 4 | PAO | PAG | POE | AB | MO | |||||||
R600 | ≤150 | 0 | 0 | A3 | CH3CH2CH2CH3 | HC | butane | 40 | 0 | 4 | 3 | 0,011 | 58,12 | -0,5 | -0,5 | 0 | 152 | 38 | 129 | MO | PAO | POE | AB | |||||||||||||||
R600a | R134a | ≤150 | 0 | 0 | A3 | CH3CHCH3CH3 | HC | isobutane | R134a, R12 | 40 | -10 | -25 | 3 | 3 | 0,011 | 58,12 | -11,8 | -11,8 | 0 | 135 | 36,3 | 115 | 55 (H) | -9 | MO | PAO | POE | AB | ||||||||||
R717 | R404A | R22 | ≤150 | 0 | 0 | B2L | NH3 | NH3 | ammonia | R404A, R507A, R22 | 12 | -20 | -15 | -50 | 0 | 0 | 0,00035 | 17,03 | -33,4 | -33,4 | 0 | 132 | 113 | 60 | 100 (M) | 60 | MO | PAO | MO/HC | AB | ||||||||
R723 | ≤150 | 0 | 0 | B2 | NH3/ R-E170 | NH3/ R-E170 | ammonia/ DME | R404A, R507A, R22 | 12 | -20 | -15 | -50 | 1 | 1 | N/A | 22,77 | -36,5 | -36,5 | 0 | 131 | 110 | 58 | 105 (M) | 35 | MO | PAO | MO/HC | AB | ||||||||||
R744 | R134a | R404A | R22 | ≤150 | 0 | 0 | A1 | CO2 | CO2 | carbon dioxide | R23, R134a, R404A, R507A | 20 | -20 | -10 | -50 | 1 | 1 | 0,07 | 44,01 | -78,3 | -78,3 | 0 | 31 | 73,8 | -11 | POE | PAG | |||||||||||
R744A | >150..750 | 0,017 | 0 | A1 | N2O | N2O | nitrous oxide | R23, R508A, R508B | -40 | -80 | 298 | 265 | N/A | 44,01 | -88,5 | -88,5 | 0 | 36 | 72,5 | -7 | special | |||||||||||||||||
R1150 | ≤150 | 0 | 0 | A3 | CH2CH2 | HC | ethylene | R14, R23, R508A, R508B | -50 | -100 | 4 | 4 | 0,006 | 28,05 | -103,8 | -103,8 | 0 | 9 | 50,4 | -19 | MO | PAO | ||||||||||||||||
R1224yd(Z) | ≤150 | 0,00012 | 0 | A1 | (Z)-CF3-CF=CHCl | HCFO | (Z)-1-chloro-2,3,3,3-tetrafluoro-propene | Amolea | R123, R11 | 30 | 0 | 4 | 1 | N/A | 14,6 | 14,6 | 0 | 156 | 33,3 | 141 | POE | |||||||||||||||||
R1233zd(E) | ≤150 | 0,00034 | 0 | A1 | C3H2ClF3 | HCFO | trans-1-chloro-3,3,3-trifluoro-1-propene | R123, R11 | 30 | 0 | 5 | 1 | N/A | 133,5 | 18,3 | 18,3 | 0 | 166 | 36,2 | 147 | POE | |||||||||||||||||
R1234yf | R134a | ≤150 | 0 | 0 | A2L | CF3FCH2 | HFO | 2,3,3,3-tetrafluoro-1-propene | Chemours, Honeywell | R134a | 25 | -25 | -30 | 4 | 1 | 0,058 | 114,04 | -29,5 | -29,5 | 0 | 95 | 33,8 | 82 | 98 (M) | -14 | POE | PVE | |||||||||||
R1234ze(E) | R134a | ≤150 | 0 | 0 | A2L | C3H2F4 | HFO | trans-1,3,3,3-tetrafluoro-1-propene | Honeywell | R134a | 40 | -10 | 6 | 1 | 0,061 | 114,04 | -19 | -19 | 0 | 109 | 36,4 | 92 | 75 (H) | -6 | POE | PVE | ||||||||||||
R1270 | R404A | R22 | ≤150 | 0 | 0 | A3 | CH2CHCH3 | HC | propylene / propene | R404A, R507A, R22 | 12 | -40 | -20 | -55 | 2 | 2 | 0,008 | 42,08 | -47,6 | -47,6 | 0 | 91 | 45,6 | 61 | 104 (M) | 12 | PAO | PAG | POE | AB | MO | |||||||
R1336mzz(E) | ≤150 | 0 | 0 | A1 | C4H2F6 | HFO | trans-1,1,1,4,4,4-hexafluoro-2-butene | R245fa | 40 | 0 | 18 | 7 | 0,048 | 164,06 | 7,6 | 7,6 | 0 | 130 | 27,66 | 126 | POE | special | ||||||||||||||||
R1336mzz(Z) | ≤150 | 0 | 0 | A1 | C4H2F6 | HFO | cis-1,1,1,4,4,4-hexafluoro-2-butene | R123, R245fa | 40 | 0 | 9 | 2 | 0,087 | 164,06 | 33,5 | 33,5 | 0 | 171 | 29 | 165 | POE | special | ||||||||||||||||
MO89 | >2500 | 0 | >0..4 | A1 | HFC | R125/ 218/ 290 | ISCEON MO89 | R13B1 | -20 | -45 | -40 | -80 | 3805 | 3324 | N/A | 113,92 | -53,2 | -50,3 | 2,9 | 62 | 35,6 | 48 | POE | PVE | AB | |||||||||||||
R404A | R404A | >2500 | 0 | >0..4 | A1 | HFC | R143a/ 125/ 134a | R502, R22 | 0 | -45 | 7 | -30 | -70 | 3922 | 3940 | 0,52 | 97,6 | -46,2 | -45,5 | 0,7 | 72 | 37,35 | 56 | 105 (M) | -34 | POE | PVE | AB | ||||||||||
R407A | R404A | R22 | >750..2500 | 0 | >4..8 | A1 | HFC | R32/ 125/ 134a | R22, R404A, R507A | 0 | -40 | 7 | -30 | -55 | 2107 | 1920 | 0,33 | 90,11 | -45,2 | -38,7 | 6,5 | 82 | 44,94 | 59 | 98 (M) | -19 | POE | PVE | AB | |||||||||
R407C | R22 | >750..2500 | 0 | >4..8 | A1 | HFC | R32/ 125/ 134a | R22, R404A, R507A | 12 | -25 | -30 | 1774 | 1620 | 0,31 | 86,2 | -43,8 | -36,7 | 7,1 | 86 | 46,15 | 61 | 100 (H) | -8 | POE | PVE | AB | ||||||||||||
R407F | R404A | R22 | >750..2500 | 0 | >4..8 | A1 | HFC | R32/ 125/ 134a | R22, R404A, R507A | 0 | -40 | 7 | -30 | -55 | 1825 | 1674 | 0,32 | 82,06 | -46,1 | -39,7 | 6,4 | 83 | 47,55 | 57 | 104 (M) | -11 | POE | PVE | AB | |||||||||
R407H | R404A | R22 | >750..2500 | 0 | >4..8 | A1 | HFC | R32/ 125/ 134a | R22, R404A, R507A | 0 | -30 | 7 | -35 | 1490 | 1380 | 0,38 | 79,1 | -44,6 | -37,6 | 7 | 87 | 48,57 | 60 | 99 (M) | -8 | POE | PVE | AB | ||||||||||
R410A | R22 | R410A | >750..2500 | 0 | 0 | A1 | HFC | R32/ 125 | R22, R13B1 | 12 | -25 | -40 | -40 | -80 | 2088 | 1920 | 0,44 | 72,59 | -51,4 | -51,4 | 0 | 71 | 49,01 | 43 | 140 (H) | -4 | POE | PVE | AB | |||||||||
R417A | R134a | R22 | >750..2500 | 0 | >4..8 | A1 | HFC | R125/ 134a/ 600 | R22 | 12 | -25 | -30 | 2346 | 2130 | 0,15 | 106,75 | -39,1 | -34,1 | 5 | 85 | 38,94 | 67 | 97 (M) | -25 | POE | PVE | AB | |||||||||||
R417B | R134a | R22 | >2500 | 0 | >0..4 | A1 | HFC | R125/ 134a/ 600 | R22 | 0 | -40 | 7 | 2920 | 2740 | 0,069 | 113,12 | -44,9 | -41,5 | 3,4 | 74 | 37,37 | 58 | 95 (M) | -37 | POE | PVE | AB | |||||||||||
R422A | R22 | >2500 | 0 | >0..4 | A1 | HFC | R125/ 134a/ 600a | R22 | 0 | -40 | 7 | 3143 | 2850 | 0,29 | 113,6 | -46,5 | -44 | 2,5 | 71 | 36,65 | 55 | 100 (M) | -39 | POE | PVE | AB | ||||||||||||
R422D | R22 | >2500 | 0 | >4..8 | A1 | HFC | R125/ 134a/ 600a | R22 | 0 | -40 | 7 | 2729 | 2470 | 0,26 | 109,94 | -43,2 | -38,3 | 4,9 | 78 | 37,95 | 62 | 90 (M) | -36 | POE | PVE | AB | ||||||||||||
R427A | R22 | >750..2500 | 0 | >4..8 | A1 | HFC | R32/ 125/ 143a/ 134a | R22 | 0 | -40 | 7 | 2138 | 2020 | 0,29 | 90,44 | -43 | -36,2 | 6,8 | 85 | 44,06 | 63 | 90 (M) | -20 | POE | PVE | AB | ||||||||||||
R437A | >750..2500 | 0 | >0..4 | A1 | HFC | R125/ 134a/ 600/ 601 | R12 | 12 | -30 | 1805 | 1640 | 0,081 | 103,71 | -32,4 | -28,9 | 3,5 | 95 | 40,03 | 75 | 108 (M) | -7 | POE | PVE | AB | ||||||||||||||
R438A | R134a | R22 | >750..2500 | 0 | >4..8 | A1 | HFC | R32/ 125/ 134a/ 600/ 601a | R22 | 0 | -40 | 7 | 2264 | 2060 | 0,079 | 99,13 | -42,3 | -35,7 | 6,6 | 83 | 41,79 | 63 | 88 (M) | -27 | POE | PVE | AB | |||||||||||
R442A | >750..2500 | 0 | >4..8 | A1 | HFC | R32/ 125/ 134a/ 152a/ 227ea | R404A, R507A | 0 | -40 | 1888 | 1750 | 0,33 | 81,76 | -46,4 | -39,7 | 6,7 | 82 | 47,48 | 57 | POE | PVE | |||||||||||||||||
R444A | R134a | ≤150 | 0 | >8 | A2L | HFO/ HFC | R32/ 152a/ 1234ze(E) | AC5 | Koura (Mexichem) | R134a | 25 | -20 | 92 | 89 | 0,29 | 96,7 | -35,7 | -24,6 | 11,1 | 106 | 44,73 | 81 | POE | PVE | ||||||||||||||
R448A | R404A | >750..2500 | 0 | >4..8 | A1 | HFO/ HFC | R32/ 125/ 1234yf/ 1234ze(E)/ 134a | N-40 | Honeywell | R404A, R507A | 12 | -40 | -45 | -25 | -65 | 1387 | 1273 | 0,388 | 86,28 | -46,1 | -39,9 | 6,2 | 83 | 45,95 | 58 | 96 (M) | 12 | POE | PVE | |||||||||
R449A | R404A | >750..2500 | 0 | >4..8 | A1 | HFO/ HFC | R32/ 125/ 1234yf/ 134a | XP40, 449A | Chemours, Arkema | R404A, R507A | 12 | -40 | -45 | -25 | -65 | 1397 | 1282 | 0,357 | 87,21 | -45,7 | -40 | 5,7 | 82 | 45 | 58 | 77 | 96 (M) | 12 | POE | PVE | ||||||||
R449C | R22 | >750..2500 | 0 | >4..8 | A1 | HFO/ HFC | R32/ 125/ 1234yf/ 134a | Chemours | R407C, R22 | 12 | -35 | 1251 | 1146 | 0,362 | -44 | -38 | 6 | 84 | 61 | 81 | POE | PVE | ||||||||||||||||
R450A | R134a | >150..750 | 0 | >0..4 | A1 | HFO/ HFC | R1234ze(E)/ 134a | N-13 | Honeywell | R134a, R12 | 25 | -25 | 604 | 547 | 0,319 | 108,67 | -23,4 | -22,8 | 0,6 | 104 | 38,2 | 86 | 88 (M) | -6 | POE | PVE | ||||||||||||
R452A | R404A | >750..2500 | 0 | >0..4 | A1 | HFO/ HFC | R32/ 125/ 1234yf | XP44 | Chemours | R404A, R507A | 12 | -40 | -25 | -65 | 2140 | 1945 | 0,423 | 103,51 | -46,9 | -43,1 | 3,8 | 75 | 40,03 | 56 | 75 | POE | PVE | |||||||||||
R452B | R404A | R410A | >150..750 | 0 | >0..4 | A2L | HFO/ HFC | R32/ 125/ 1234yf | XL55, L-41y | Chemours, Honeywell | R410A | 15 | -25 | 698 | 676 | 0,062 | 63,53 | -50,7 | -49,8 | 0,9 | 77 | 52,2 | 46 | 65 | 98 (H) | 7 | POE | PVE | ||||||||||
R454A | R404A | >150..750 | 0 | >4..8 | A2L | HFO/ HFC | R32/ 1234yf | XL40, ARM-20b | Chemours, Arkema | R404A, R507A | 12 | -40 | -25 | -65 | 239 | 238 | 0,056 | 79,79 | -47,9 | -42,2 | 5,7 | 82 | 46,3 | 57 | 76 | POE | PVE | |||||||||||
R454B | R410A | >150..750 | 0 | >0..4 | A2L | HFO/ HFC | R32/ 1234yf | XL41 | Chemours | R410A | 15 | -25 | 466 | 467 | 0,061 | 62,61 | -50,5 | -49,5 | 1 | 78 | 52,67 | 47 | 66 | 97 (H) | 0 | POE | PVE | |||||||||||
R454C | R404A | ≤150 | 0 | >4..8 | A2L | HFO/ HFC | R32/ 1234yf | XL20 | Chemours | R404A, R507A | 12 | -40 | -25 | -65 | 148 | 146 | 0,059 | 90,78 | -45,6 | -37,8 | 7,8 | 86 | 43,2 | 64 | 83 | POE | PVE | |||||||||||
R455A | R404A | ≤150 | 0 | >8 | A2L | HFO/ HFC | R32/ 1234yf/ 744 | L-40X | Honeywell | R404A, R507A | 12 | -40 | -25 | -65 | 148 | 146 | 0,105 | 87,45 | -52 | -39,2 | 12,8 | 86 | 46,5 | 61 | 93 (M) | 10 | POE | PVE | ||||||||||
R456A | R134a | >150..750 | 0 | >4..8 | A1 | HFO/ HFC | R32/ 1234ze(E)/ 134a | AC5X | Koura (Mexichem) | R134a | 25 | -25 | 687 | 627 | 0,32 | 101,42 | -30,8 | -25,4 | 5,4 | 103 | 41,75 | 80 | POE | PVE | ||||||||||||||
R457A | R404A | ≤150 | 0 | >4..8 | A2L | HFO/ HFC | R32/ 1234yf/ 152a | ARM-20a | Arkema | R404A, R507A | 12 | -40 | -25 | -65 | 139 | 139 | 0,043 | 87,61 | -42,6 | -35,5 | 7,1 | 90 | 43,08 | 68 | 85 | POE | PVE | |||||||||||
R463A | >750..2500 | 0 | >8 | A1 | HFO/ HFC | R32/ 125/ 1234yf/ 134a/ 744 | XP41 | Chemours | R410A | 15 | -25 | 1494 | 1377 | 0,299 | 74,72 | -59,9 | -46,9 | 13 | 76 | 52,44 | 47 | 65 | POE | PVE | ||||||||||||||
R465A | R404A | ≤150 | 0 | >8 | A2 | HFO/ HFC | R32/ 1234yf/ 290 | ARM-25 | Arkema | R404A, R507A | 7 | -40 | 145 | 143 | 0,04 | 82,9 | -51,7 | -40 | 11,7 | 82 | 43,36 | 60 | POE | PVE | ||||||||||||||
R466A | R410A | >150..750 | 0 | >0..4 | A1 | HFO/ HFC | R32/ 1234yf/ 13I1 | N-41 | Honeywell | R410A | 15 | -25 | 733 | 696 | 0,099 | 80,69 | -51,7 | -51 | 0,7 | 76 | 51,44 | 46 | 65 | POE | PVE | |||||||||||||
R468A | R404A | ≤150 | 0 | >8 | A2L | HFO/ HFC | R32/ 1234yf/ 1132a | Daikin Chemical | R404A, R507A, R22 | 0 | -40 | 148 | 147 | N/A | 88,8 | -51,2 | -39 | 12,2 | 84 | 44,54 | 62 | POE | ||||||||||||||||
R469A | >750..2500 | 0 | >8 | A1 | HFC/ CO2 | R744/ 32/ 125 | WT69 | TEGA | R23 | -40 | -75 | 1358 | 1250 | N/A | 59,1 | -78,5 | -61,5 | 17 | 59 | 65,17 | 23 | POE | ||||||||||||||||
R471A | R134a | ≤150 | 0 | >0..4 | A1 | HFO/ HFC | R1234ze(E)/ 1336mzz(E)/ 227ea | Honeywell | (R134a) | 20 | -20 | 148 | 148 | N/A | 122,09 | -16,9 | -13,7 | 3,2 | 112 | 35,34 | 97 | 67 (H) | -7 | POE | ||||||||||||||
R500 | >2500 | 0,74 | 0 | A1 | CFC | R12/ 152a | 10 | -30 | 8077 | 7560 | 0,4 | 99,3 | -33,6 | -33,6 | 0 | 102 | 41,68 | 78 | MO | AB | ||||||||||||||||||
R502 | R404A | >2500 | 0,33 | 0 | A1 | CFC | R22/ 115 | 10 | -50 | 4657 | 4790 | 0,45 | 111,64 | -45,4 | -45,4 | 0 | 82 | 40,7 | 60 | AB | ||||||||||||||||||
R503 | >2500 | 0,6 | 0 | A1 | CFC | R13/ 23 | -50 | -90 | 14560 | 13300 | 0,35 | 87,24 | -87,9 | -87,9 | 0 | 20 | 43,43 | -2 | AB | |||||||||||||||||||
R507A | R404A | >2500 | 0 | 0 | A1 | HFC | R143a/ 125 | R502, R22 | 0 | -45 | 7 | -30 | -70 | 3985 | 3990 | 0,53 | 98,86 | -46,7 | -46,7 | 0 | 71 | 37,05 | 54 | 107 (M) | -34 | POE | PVE | AB | ||||||||||
R508A | >2500 | 0 | 0 | A1 | HFC | R23/ 116 | R503 | -50 | -95 | 13210 | 11600 | 0,23 | 100,1 | -87,6 | -87,6 | 0 | 10 | 36,48 | -3 | POE | ||||||||||||||||||
R508B | >2500 | 0 | 0 | A1 | HFC | R23/ 116 | R503 | -50 | -95 | 13400 | 11700 | 0,25 | 95,39 | -87,6 | -87,6 | 0 | 11 | 37,71 | -3 | POE | ||||||||||||||||||
R513A | R134a | >150..750 | 0 | >0..4 | A1 | HFO/ HFC | R1234yf/ 134a | XP10 | Chemours | R134a, R12, R404A | 25 | -25 | -30 | 631 | 573 | 0,319 | 108,31 | -29,6 | -29,5 | 0,1 | 95 | 36,5 | 78 | 102 (M) | -7 | POE | PVE | |||||||||||
R514A | ≤150 | 0 | 0 | B1 | HFO | R1336mzz(Z)/ 1130(E) | XP30 | Chemours | R11, R123, (R134a) | 40 | 0 | 7 | 2 | 0,013 | 139,6 | 28,8 | 28,8 | 0 | 178 | 34,7 | 161 | POE | ||||||||||||||||
R515B | R134a | >150..750 | 0 | 0 | A1 | HFO/ HFC | R1234ze(E)/ 227ea | N-15 | Honeywell | R134a | 20 | -20 | 293 | 299 | 0,29 | 117,48 | -18,8 | -18,8 | 0 | 109 | 35,84 | 93 | 75 (H) | -7 | POE | |||||||||||||
R516A | R134a | ≤150 | 0 | 0 | A2L | HFO/ HFC | R1234yf/ 152a/ 134a | ARM-42 | Arkema | R134a | 25 | -25 | 142 | 131 | 0,042 | 102,58 | -29,4 | -29,4 | 0 | 97 | 36,23 | 80 | POE |
Refrigerant | similar to R134a | similar to R404A | similar to R22 | similar to R410A | GWP range | ODP | Temperature glide range | Safety group ISO817 | Chemical | Group | Components | Name | Manufacturer | Substitute for | Application max. (°C) | Application min. (°C) | Application limited max. (°C) | Application limited min. (°C) | Application 2-stage max. (°C) | Application 2-stage min. (°C) | GWP AR4 | GWP AR5 | Practical limit AEL (kg/m3) | Molar mass | Normal boiling point (°C) | Normal dew point (°C) | Temperature glide (K) | Critical temperature (°C) | Critical pressure (bar) | Condensing temperature at 26 bar abs (°C) | Condensing temperature at 40 bar abs (°C) | Relative refrigerating capacity (%) | Discharge gas temperature increase (K) | Oil 1 | Oil 2 | Oil 3 | Oil with limitations 1 | Oil with limitations 2 |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|