R502
The following table shows the data for R502 and alternative refrigerants.
ODP: ozone depletion potential
GWP: global warming potential according to EN 378:2017; AR4: Fourth Assessment Report of the IPCC, AR5: Fifth Assessment Report of the IPCC, AR6: Sixth Assessment Report of the IPCC
pract. limit AEL: assigned exposure limit according to EN 378:2017
Temperature glide: Total glide from bubble to dew line, based on 1.013 bar. Real glide depends on operating conditions.
Relative refr. capacity and discharge temp. increase: Reference refrigerants are those listed under "Substitute for", performance data are average values based on calorimeter tests.
(H): high temperature application
(M): medium temperature application
(L): low temperature application
Data is based on publications of various refrigerant manufacturers and is subject to change.
R502 | R404A | R507A | R22 | |
---|---|---|---|---|
Chemical | CHClF2 | |||
Group | CFC | HFC | HFC | HCFC |
Components | R22/ 115 | R143a/ 125/ 134a | R143a/ 125 | |
Name | chloro-difluoro-methane | |||
Manufacturer | ||||
Substitute for | R502, R22 | R502, R22 | R502, R12 | |
Application max (°C) | 10 | 0 | 0 | 12 |
Application min (°C) | -50 | -45 | -45 | -45 |
Appl. limitations max (°C) | 7 | 7 | ||
Appl. limitations min (°C) | ||||
Appl. 2-stage max (°C) | -30 | -30 | -20 | |
Appl. 2-stage min (°C) | -70 | -70 | -50 | |
Oil 1 | AB | POE | POE | MO |
Oil 2 | PVE | PVE | AB | |
Oil 3 | ||||
Oil with limitations 1 | AB | AB | ||
Oil with limitations 2 | ||||
Molar mass | 111,64 | 97,6 | 98,86 | 86,47 |
Normal boiling point (°C) | -45,4 | -46,2 | -46,7 | -40,7 |
Normal dew point (°C) | -45,4 | -45,5 | -46,7 | -40,7 |
Temperature glide (K) | 0 | 0,7 | 0 | 0 |
Crit. temp. (°C) | 82 | 72 | 71 | 96 |
Crit. pressure (bar) | 40,7 | 37,35 | 37,05 | 49,9 |
ODP | 0,33 | 0 | 0 | 0,055 |
GWP AR4 | 4657 | 3922 | 3985 | 1810 |
GWP AR5 | 4790 | 3940 | 3990 | 1760 |
GWP AR6 | 4728 | 4775 | 1960 | |
Cond. temp. at 26 bar abs (°C) | 60 | 56 | 54 | 63 |
Cond. temp. at 40 bar abs (°C) | ||||
Relative refr. capacity (%) | 105 (M) | 107 (M) | 80 (L) | |
Discharge temp. increase (K) | -34 | -34 | 35 | |
Safety class | A1 | A1 | A1 | A1 |
Pract. limit AEL (kg/m³) | 0,45 | 0,52 | 0,53 | 0,3 |