Thermostat for solenoid valve
- Use a high-quality design, suitable for sensor temperatures of up to 120°C.
- Temperature setting:
- CSH compressors ON 110°C / OFF 100°C (ECO operation with liquid injection using a compressor from the CSH series as an example)
- HS./OS. compressors ON 100°C / OFF 90°C (liquid injection in combination with refrigerant R717 (ammonia) only after consulting BITZER!)
- Mount the thermostat sensor on the discharge gas line:
- Smooth the pipe carefully at the contact surface and clean the surface until it is metallically bright.
- Apply a heat transfer paste to the contact surface.
- Fix the sensor with stable pipe clamps. Take the heat expansion into account!
- Insulate the sensor.