Mounting the electromagnetic clutch
NOTICE
Risk of damage to the compressor due to wrong couplings!
Risk of damage to the compressor due to wrong couplings!
Use only couplings approved by BITZER !
NOTICE
Risk of damage to the compressor.
Risk of damage to the compressor.
Tighten screws and nuts only to the prescribed tightening torque and, if possible, crosswise in at least 2 steps.
NOTICE
Observe the Operating Instructions and installation instructions of the clutch manufacturer!
Observe the Operating Instructions and installation instructions of the clutch manufacturer!
1 | Bearing flange | |
2 | Woodruff key | |
3 | Cable | |
4 | Magnet | |
5 | Screws M8x30 DIN 912 | |
6 | Rotor | |
7 | Nuts M8 | |
8 | Pulley | |
9 | Retaining ring with lugs DIN 984 form JK | |
10 | Straining screw | |
11 | Stud screws M8x20 |
- Fasten the magnet (4) to the housing. Insert the screws (5) and tighten them crosswise (tightening torque 25 Nm).
- Mount the Woodruff key (2).
- Grease the straining screw (10). Slide the rotor (6) on the shaft and magnet (4). Screw the straining screw (10) into the shaft end. Recommended tightening torque is 85 Nm, unless otherwise specified by the clutch manufacturer.
- Slide the pulley over the stud screws of the clutch and tighten with nuts (7) (tightening torque 25 Nm).
- Connect the cable (3) (independent of polarity), keeping it away from hot parts (tmax = 105°C).
NOTICE
Gripping or abradant pulleys will cause damage to the magnet.
Gripping or abradant pulleys will cause damage to the magnet.
You must be able to turn the pulley by hand without abrading the magnet.
Adjust the air gap accordingly!
Instructions for the installation of other clutches upon request.