Used oil from systems with A3 or A2L refrigerants
NOTICE
Fire hazard!
Fire hazard!
The used oil contains a relatively large amount of dissolved refrigerant.
Pack used oil safely. Dispose of in an environmentally friendly manner.
- Hydrocarbons, for example propane, R290 or propene, R1270 and low-fluorinated flammable refrigerants, for example R1234yf, dissolve very well in refrigeration compressor oil at room temperature. This also applies to blends containing these substances.
- Used oil from such systems may still contain relatively high percentages of dissolved flammable gases even at atmospheric pressure. These components gas out.
- Observe during storage and transport:
- Fill used oil into pressure resistant vessels.
- Fill vessels with nitrogen as a protective gas and close them.
- Mark them, e. g. with the warning sign "flammable substance" W021 from ISO7010.