Cycling rate and minimum running times

Be sure to adhere to the following minimum times:

Cycling rate and minimum running times for scroll compressors with frequency inverter

Compressor

Minimum running time

Cycling rate (minimum start-to-start time)

GSD6, GSU6(Orbit 6)

2 min

5 min

GED8, GSD8, GSU8 (Orbit 8)

3 min

5 min

ESH7, ELH7

3 min

5 min

ELV21

2 min

see Operating Instructions

  • ESB-310: Operating instructions Semi-hermetic scroll compressors ELV21

ELV52

2 min

see Operating Instructions

  • ESB-320: Operating instructions Semi-hermetic scroll compressors ELV(E)52
Risk of motor failure!

Risk of motor failure!

The control logic of the superior system controller must meet the specified requirements in any case.