Avoid entry of non condensable gases and moisture.
Install a generously sized drier – design and dimensions according to manufacturer’s specifications.
Use moisture indicators with defined display of the degree of drying (< 50 ppm).
For tightness tests and high-pressure tests, use preferably dried nitrogen. When testing with dried air, the compressor must not be included (keep shut-off valves closed!).
Use two-stage vacuum pumps with gas ballast (1.5 mbar “standing vacuum”) to avoid condensation of water vapour. Use large connection dimensions.
Keep compressor shut-off valves closed until the last evacuation process!