HS.53 ..74 with SE-i1, PW start, basic sensor kit
Last revision of the diagram:
01.10.2018
Abbr | Component | |
---|---|---|
B1 | Oil thermostat ① | |
B2 | Control unit (cooling demand) or command for compressor start (release signal from the system controller) or controller On/Off | |
B6 | High pressure transmitter | |
B7 | Low pressure transmitter | |
F1 | Main fuse | |
F2 | Compressor fuse | |
F3 | Control circuit fuse | |
F4 | Oil heater fuse | |
F5 | High-pressure switch | |
F6 | Low pressure switch | |
F7 | Oil flow switch | |
F9 | Monitoring of oil stop valve | |
F10 | Oil filter monitoring | |
F12 | ECO control unit; pressure switch (ECO) (ATEX) | |
F13 | Thermal overload relay "motor" PW1; star-delta: thermal overload relay "motor" | |
F14 | Thermal overload relay "motor" PW2; star-delta: – | |
F17 | Control transformer fuse | |
F21 | Fuse of the heating element in the terminal box (only for HS.64 .. HS.74) | |
F30 | Fuse of compressor protection device | |
H1 | Signal lamp "motor failure" (overtemperature/phase failure) | |
H2 | Signal lamp “pause time” | |
H4 | Signal lamp “oil level fault” | |
H5 | Signal lamp "oil stop valve fault” | |
K1 | Contactor "1st part winding" (PW) or main contactor (star-delta) or compressor contactor (DOL or FI or soft starter) | |
K2 | Contactor "2st part winding" (PW) or delta contactor (star-delta) | |
K3 | Auxiliary relay or star contactor (star-delta) | |
K4 | Auxiliary contactor “oil level” | |
K1T | Time relay “oil flow monitoring” HS.85: oil supply monitoring 20 s | |
K2T | Time relay “pause time” 300 s | |
K3T | Time relay "part winding" 0.5 s or "star-delta start" 1 s "star-delta start" only HS.85: 1.5 .. 2 s | |
K4T | Time relay "oil level monitoring 120 s" ① | |
K5T | Time interval relay "CR4" flashing function on / off 10 s | |
M1 | Compressor | |
N1 | Frequency inverter (FI) | |
N3 | Soft starter | |
Q1 | Main switch | |
R1 | Oil heater ① | |
R2 | Discharge gas temperature sensor | |
R3..8 | PTC sensor in motor | |
R9 | Heating element for terminal box (only for HS.53 .. HS.74) | |
R10 | Optional temperature sensor | |
R11 | Auxiliary resistor | |
S1 | Control switch (on/off) | |
S2 | Fault reset "motor & discharge gas temperature, motor rotation direction, oil flow" and for HS.85: Fault reset "motor & discharge gas temperature, motor rotation direction, oil supply” | |
S3 | Cancellation “pause time” | |
S4 | Fault reset “oil filter chamber” (HS.85) | |
T1 | Control transformer (example for 230 V, required according to EN60204-1) | |
U | Interference suppressor: varistor or RC element integrated into the solenoid valve plug if required | |
Y2 | Solenoid valve "oil injection" | |
Y2 | Solenoid valve "liquid line" | |
Y3 | Solenoid valve “shut-down bypass” | |
Y4 | Solenoid valve "capacity regulator CR1" | |
Y5 | Solenoid valve "capacity regulator CR2" | |
Y6 | Solenoid valve "capacity regulator CR3" | |
Y7 | Solenoid valve "capacity regulator CR4" | |
Y8 | Solenoid valve "ECO" (if required) |
①: Components are included in the scope of delivery of the oil separator
OLC-D1: Opto-electronic liquid level monitoring. Included in the extent of delivery of the oil separator.
SE-B*: Protection device for oil flow monitoring and oil filter monitoring
Technical documents for further information: