Compressor repair with no Ex zone - exchange valve plate
Example task: Exchange of a valve plate on a semi-hermetic reciprocating compressor operated with A2L refrigerant R454C. The compressor is located on a rack in a machinery room.
Special tools or preconditions:
- Mobile A2L gas detector
- A2L leak detector
- A2L fire extinguisher
- A2L recovery equipment
- Vacuum pump with external switch, outside room
- Extra fan
- A2L anti-sparking tool – not necessary
- Avoid Ex zone! Avoid / check for leakage!
Working steps or preconditions:
- Educated worker
- Read / inform for risk assessment of system
- Have A2L fire extinguisher ready
- Put warning sign to notify work in progress, especially where refrigerant might be released
- Power off compressor / system
- Ventilation on
- a. Install extra fan
- Go in with gas detector / check regularly with gas detector or machinery room detector
- Close compressor shut off valves
- Release pressure
- a. Small gaseous amount to marked outside area
- Oil heater on
- Evacuate compressor
- a. Release vacuum pump outlet to marked outside area
- Charge compressor with Nitrogen
- Open compressor and replace valve plate
- a. Observe gas concentration at working place with mobile gas detector
- b. Stop work, if gas concentration reaches alarm level and wait for ventilation!
- Close compressor
- Check tightness with dry Nitrogen
- Evacuate compressor
- Open compressor shut off valves
- Remove warning signs
- Take compressor into operation again