Retrofit of R404A/R507A systems
1. | Data protocol at stable operation with present refrigerant. |
2. | Switch off system. |
3. | Reclaim the refrigerant with appropriate reclaim unit, down to ambient pressure:
|
4. | If necessary, adjust high and low pressure switches. |
5. | Close the compressor shut off valves. |
6. | If necessary, change elastomer gaskets in the compressor (Compatibility of BITZER products):
|
7. | On open type compressors change the shaft seal. |
8. | Drain compressor and (if applicable) separator oil and charge new polyolester oil:
|
9. | Change filter drier. |
10. | Change insert of suction line filter, if existing. Install suction line filter, if dirt appears or chemical stability of the system is questionable. |
11. | Adjust or replace the expansion valves:
|
12. | Change elastomer gaskets of valves, control apparatus aso. or replace these components. |
13. | Further remove refrigerant with reclaim unit and subsequently evacuate down to 3 to 5 mbar standing vacuum. |
14. | Tightness test:
|
15. | Charge new refrigerant into the liquid reciever:
|
16. | Commissioning according to the operating instructions of the system:
|
17. | If necessary, add refrigerant via the suction line:
|
18. | If necessary, adjust the control apparatus. |
19. | Data protocol at stable operation with the new refrigerant. |
20. | Mark the system with stickers with the new refrigerant denomination. |
21. | Record the changes in the system log book. |
22. | Check the oil level at stable operation. |
23. | Dispose of or recycle the reclaimed refrigerant. |
24. | Dispose of the used oil. |
25. | Check the operating conditions and oil level after 10 to 24 hours:
|
26. | Check the tightness of the system and the elastomer gaskets in the months following the re-commissioning. |