Necessary preparations before retrofit of R404A/R507A to R448A/R449A

Checklist 1: Note conditions before retrofit

Design operating conditions or application range, like medium temperature or low temperature refrigeration, ...

Year of establishment.

Refrigerating capacity at design operating conditions.

Current refrigerating capacity demand at design operating conditions:

Current refrigerant.

Compressor:

  • Model, manufacturer, year of manufacture.

Expansion devices:

  • Design (thermostatic expansion valve, electronic EV, ...).
  • Model, manufacturer, orifice size/capacity step.

Solenoid valves:

  • Model, manufacturer, ...

Pressure controls:

  • Evaporator pressure, crankcase pressure, condenser pressure regulators aso.
  • Model, manufacturer, ...

Filter drier:

  • Model, manufacturer, ...

Heat exchangers (evaporators, condensers, desuperheaters, internal heat exchangers, ...):

  • Design, operation in counter flow, parallel flow or other.
  • Model, manufacturer, ...

Oil:

  • Type, manufacturer.
  • Oil analysis for humidity, acid, colour aso. recommended.

Visible damages, dirt aso.

Checkliste 2: Further preparations before retrofit

New refrigerant (Refrigerant comparison to R404A/R507A).

New refrigerant stickers.

Oil:

  • Oil change is recommended.
  • Use only original oils, that are compatible and proven with HFO refrigerants (blend components in R448A, R449A).

Compressor:

  • Manufacturers statement on compatibility.
  • If necessary, new gaskets.

Expansion devices:

Solenoid valves:

  • Manfacturers statement on compatibility.
  • If necessary, new gaskets.

Filter drier:

  • New filter drier is recommended.

Pressure controls:

  • Manfacturers statement on compatibility.
  • If necessary, new gaskets.

For screw compressors the necessity to install or enlarge the oil cooler is checked. Calculations are done with the BITZER SOFTWARE.

Bottles for disposal or recycling of refrigerant.

Container/bottles for disposal of oil.

Availability of appropriate tools and test equipment.